Silentknight SD505-6RB 6 Relay Base Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Sécurité Silentknight SD505-6RB 6 Relay Base. SilentKnight SD505-6RB 6 Relay Base User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 2
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
P/N 151192
SILENT
KNIGHT
®
SD505-6RB (6
Relay Base)
Installation Instructions
This sheet is intended to be used to install the
SD505-6RB to a Silent Knight Addressable
control panel. Refer to the control panel
installation manual for programming
instructions (P/N 151139 or 151209).
The SD505-6RB adds a relay output function to
a Silent Knight addressable detector. The Form
C relay is rated at 8.0 amps for 240 VAC, 120
VAC and 30 VDC applications.
Specifications
Wirin
g
This section contains information on how to
wire the SD505-6RB to the SLC Loop of the
control panel, how to wire the SD505-6RB to the
6” detector base, and wiring guide lines for each.
Figure 1 illustrates how to run the wiring for the
SLC loop and relay through the extension base,
and how wiring harness 140675 connects to the
6” detector base.
Note: Low and high voltage wiring must be run through
separate openings on the extension base. See
Figure 1. If you are connecting both power limited
and non-power limited sources to the relay base,
you must use one of the following types of wire,
FPLP, FPLR, or FPL within the box in accordance
to NEC 760.54.
Figure 1: Wiring Parameters
SLC Wiring
The SD505-6RB can be configured for either
Class A (Style 6) or Class B (Style 4)
supervision.
Class A (Style 6)
Figure 2 illustrates how to wire the SD505-6RB
to the SLC loop connectors for Class A (Style 6)
supervision.
Figure 2: Class A (Style 6) SLC Wiring
Parameter Rating
Relay Contact Rating:
8.0 A @ 30 VDC
8.0 A @ 240/120 VAC
SLC Operating Voltage: 32 VDC
SLC Current for Battery
Calculation:
.082 mA (Alarm and
Standby)
Operating Temperature: 32° - 120° F (0° - 49° C)
Humidity: 10-85% RH
Max. SLC Loop Resistance: 50
Supervised
Power Limited
Vue de la page 0
1 2

Résumé du contenu

Page 1 - SLC Wiring

P/N 151192SILENT KNIGHT®SD505-6RB (6″ Relay Base) Installation InstructionsThis sheet is intended to be used to install the SD505-6RB to a Silent Knig

Page 2 - Mounting the SD505-6RB

Model SD505-6RB Installation Instructions2 P/N 1511927550 Meridian CircleMaple Grove, MN 55369-4927612-493-6455800-328-0103Fax: 612-493-6475© 1999 Sil

Commentaires sur ces manuels

Pas de commentaire