Page 1 - MODEL 5499

Distributed Power ModuleMODEL 5499Installation andOperations ManualDocument 15125308/12/13 Rev L151253:L ECN 13-00708

Page 2

5499 Distributed Power Module Installation Manual6 151253You can select which input controls which output, and which inputs are Class A and Class B us

Page 3 - Contents

Installation151253 7Section 4InstallationBefore installing the 5499, the AC input must first be wired into the building’s main electrical power throug

Page 4

5499 Distributed Power Module Installation Manual8 1512534.2 Wire RoutingTo avoid induced noise (transfer of electrical energy from one wire to anothe

Page 5 - Introduction

Installation151253 94.3 Current Requirements (Standby and Alarm)4.3.1 Current Drawn From Host Panel Table 4-1 shows the 5499 current draw requirements

Page 6 - UL Requirements

5499 Distributed Power Module Installation Manual10 151253Table 4-2: Battery Calculation WorksheetDeviceNumber of DevicesCurrent per DeviceStandby Cur

Page 7 - System Overview

Installation151253 114.4 Connecting the 5499 to a Control PanelFigure 4-2 shows the general layout of the 5499 PC board. This section also provides sp

Page 8 - 3.2 Signal Input Terminals

5499 Distributed Power Module Installation Manual12 1512534.4.1 Common Trouble Relay The 5499 has a Form C trouble relay built into Terminals 11-13. T

Page 9 - 151253 5

Installation151253 134.5 Notification Appliance WiringNote:Not all devices can use the sync feature. Be sure to check Appendix A to ensure the device

Page 10 - DIP switch settings

5499 Distributed Power Module Installation Manual14 151253pass the added current load from notification appliances.Figure 4-4 Class A Supervised Inpu

Page 11 - Installation

Installation151253 15Class B Supervised Input CircuitsFigure 4-5 shows Class B supervised wiring from a fire alarm control panel to the 5499.Use an EO

Page 13 - 151253 9

5499 Distributed Power Module Installation Manual16 1512534.7 Battery ConnectionUse two 12 VDC, 7 AH gel cell batteries inside the 5499 cabinet. For b

Page 14

Installation151253 174.8 DIP Switch SettingsA 7-position DIP switch on the 5499 board allows you to select the following:• How long the 5499 will wait

Page 15 - 151253 11

5499 Distributed Power Module Installation Manual18 1512534.8.1 Selecting the Standard Input/Output ConfigurationsFigure 4-7 and Figure 4-8 show the p

Page 16 - 4.4.1 Common Trouble Relay

Installation151253 194.8.1.1 Input/Output Configurations That Select ANSI Temporal-Coded OutputsThe DIP switch settings marked with an asterisk (*) in

Page 17 - 151253 13

5499 Distributed Power Module Installation Manual20 1512534.8.2 Selecting Synchronized Output ConfigurationsThe following sections describe how to con

Page 18 - 14 151253

Installation151253 214.8.2.3 Selecting Synchronized System Sensor ConfigurationsTo select the input/outputs for System Sensor synchronized appliances,

Page 19 - 151253 15

5499 Distributed Power Module Installation Manual22 1512534.8.3 Setting the Loss of AC DelayNormal selection for reporting loss of AC is 3 hours.The O

Page 20 - 4.7 Battery Connection

Sample Applications151253 23Section 5Sample ApplicationsThe drawings in this section show various 5499 configurations, including “daisy-chaining”.5.1

Page 21 - 4.8 DIP Switch Settings

5499 Distributed Power Module Installation Manual24 151253Note:When multiple power supplies are used with one control unit they will not sync with eac

Page 22

Sample Applications151253 25Figure 5-5 Each Control NAC Activates Five Output NACs5.2 Non-Resettable Power ApplicationThe 5499 provides a dedicated 3

Page 23 - Temporal-Coded Outputs

151253 iContentsSection 1Introduction ...

Page 24

5499 Distributed Power Module Installation Manual26 1512535.3 Door Holder ApplicationIn a typical door holder application, the door holder power must

Page 25 - 151253 21

Troubleshooting151253 27Section 6TroubleshootingLight-emitting diodes (LEDs) indicate fault conditions. This section describes the LED states.6.1 LEDs

Page 26 - 22 151253

5499 Distributed Power Module Installation Manual28 1512536.2 Trouble ConditionsNote: While Input 1 & 2 are activated, Input 1 & 2 will not op

Page 27 - Sample Applications

Troubleshooting151253 296.3 Earth Fault ResistanceTable 6-1 lists the earth fault resistance detection for each applicable terminal on the FACP.Table

Page 28 - 24 151253

5499 Distributed Power Module Installation Manual30 1512536.4 Removing and Replacing the Control PanelThis section provides instruction on how to remo

Page 29 - 151253 25

Troubleshooting151253 31supply.

Page 30 - 5.3 Door Holder Application

5499 Distributed Power Module Installation Manual32 151253

Page 31 - Troubleshooting

151253 33Appendix AUL Listed Notification AppliancesFor proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on ea

Page 32 - 6.2 Trouble Conditions

5499 Distributed Power Module Installation Manual34 151253Faraday446 Vibrating Bell 476 Vibrating Bell477 Single Stroke Bell2700 -M. -R, -T, -Y, -Z St

Page 33 - 6.3 Earth Fault Resistance

UL Listed Notification Appliances151253 35Faraday(cont.)5510 Strobe5511 Strobe5512 Strobe5516 Strobe5517 Strobe5518 Strobe5519 Strobe5521 4” Square Sy

Page 34 - 30 151253

5499 Distributed Power Module Installation Manualii 1512534.8.4 Setting the Auxiliary Output ...

Page 35 - 151253 31

5499 Distributed Power Module Installation Manual36 151253FCIS2415-FC StrobeS241575-FC StrobeS2430-FC Strobe130-3117C Mini Horn130-3147C Mini HornBLV-

Page 36 - 32 151253

UL Listed Notification Appliances151253 37FCIP2430W-FC Horn/StrobeP2430K-FC Horn/StrobeP2475-FC Horn/StrobeP2475W-FC Horn/StrobeP2475K-FC Horn/StrobeP

Page 37 - Appendix A

5499 Distributed Power Module Installation Manual38 151253GentexGEC-24-15xxHorn/StrobeGEC-24-30xxHorn/StrobeGEC-24-60xxHorn/StrobeGEC-24-75xxHorn/Stro

Page 38 - 34 151253

UL Listed Notification Appliances151253 39Gentex(cont.)GES24-177xStrobeGES3-24xMulti Candella StrobeGESR-24xMulti Candella StrobeGEH-24xHornST24-30xSt

Page 39 - 151253 35

5499 Distributed Power Module Installation Manual40 151253System SensorCHRxChimeCHWxChimeCHSRxx2-Wire Chime/StrobeCHSWxx2-Wire Chime/StrobeHRxxHornHWx

Page 40 - 36 151253

UL Listed Notification Appliances151253 41System Sensor(cont.)PC4Wxx4-Wire Horn/StrobeP4WHxx4-Wire Horn/Strobe High CandelaPC4WHxx4-Wire Horn/Strobe H

Page 41

5499 Distributed Power Module Installation Manual42 151253WheelockAH-12xHornAH-24xHornAH-12WPxHorn WeatherproofAH-24WPxHorn WeatherproofAMT-241575WxxM

Page 42 - 38 151253

UL Listed Notification Appliances151253 43Wheelock(cont.)CH90-24MCCHxChime/StrobeHS-24xHornHS4-241575WxxHorn/StrobeHS4-24MCWxxHorn/StrobeHS4-24MCWHxxH

Page 43 - 151253 39

5499 Distributed Power Module Installation Manual44 151253Wheelock (cont.)RSS-121575WxStrobeRSS-241575WxStrobeRSS-24MCCxStrobeRSS-24MCCRxStrobeRSS-24M

Page 44 - 40 151253

UL Listed Notification Appliances151253 45Wheelock(cont.)RSSWP-24MCWHxStrobe Weatherproof ZRS-MCWHxStrobeZRS-24MCCxStrobeZRS-24MCCHxStrobeMB-G6-24 Mot

Page 45

151253 1Section 1IntroductionThe 5499 is a notification appliance circuit and auxiliary power expander that provides up to 9 amps of filtered, 24 volt

Page 46 - Wheelock

5499 Distributed Power Module Installation Manual46 151253

Page 47 - 151253 43

Silent Knight Fire Product Warranty and Return PolicyGeneral Terms and Conditions• All new fire products manufactured by Silent Knight have a limited

Page 48 - 44 151253

Advanced Replacement Policy• Silent Knight offers an option of advance replacement for fire product printed circuit boards that fail during the first

Page 49 - 151253 45

Manufacturer Warranties and Limitation of LiabilityManufacturer Warranties. Subject to the limitations set forth herein, Manufacturer warrants that th

Page 52

Silent Knight12 Clintonville RoadNorthford, CT 06472-1610203-484-7161Fax: 203-484-7118www.silentknight.com

Page 53 - Warn-HL-08-2009.fm

5499 Distributed Power Module Installation Manual2 151253Section 2UL RequirementsWhen installed in accordance with NFPA 70 and NFPA 72 standards, the

Page 54

System Overview151253 3Section 3System Overview3.1 Terminal Descriptions and Electrical RatingsCAUTIONEach output circuit is rated at 3 amps. DO NOT

Page 55

5499 Distributed Power Module Installation Manual4 1512533.2 Signal Input TerminalsTerminals 14 through 19 are polarized signal input terminals. They

Page 56

System Overview151253 53.3 Notification Appliance Circuit TerminalsTerminals 3 through 10 are the notification appliance circuit output terminals. Eac